Statement of Work FAA-C90-420

Exterior Door Replacement Project

Chicago Heights VORTAC

1 West Lincoln Highway (US30)
Ford Heights, IL 60411

Central Service Area

Prepared By:

Federal Aviation Administration
Chicago Technical Support Center
AJW-C22D
Elgin, Illinois

23 November, 2021

Dated 

Table of Contents

Section 

Section Title 

Table of Contents 

23 November, 2021 

II‐III 

Chicago VORTAC Vicinity/Location Map 

23 November, 2021

Specification Section 

Title 

Second 

00 11 10 

23 November, 2021 

General Requirements 

09 90 11 

Steel doors, frames, and Hardware 

23 November, 2021 

Appendix I

Schedule of Submittals

23 November, 2021 

FAA‐C90‐420 
23 November, 2021 
2‐9‐A22
rbeo3)3U
ahHonL
sWARV
tgHgch–ayiii10I
shedoI
2‐9‐A22
rbeo3)3U
ahHonL
sWARV
tgHgch–aniao10I
shedoI
SECTION  09 90 11 – STEEL DOORS, FRAMES, AND 
HARDWARE 

PART 1 – GENERAL REQUIREMENTS 

1.01 SCOPE OF WORK 

A. This specification applies to the work stated in Section 01 00 10 of 
this statement of work to replace two (2) asbestos insulated, metal 
exterior doors and hardware.  

B. The new exterior doors shall match the existing doors regarding door 
size, swing, UL/fire rating, interior and exterior hardware (type, 
quantity, and finish). 

1.02 APPLICABLE PUBLICATIONS 

American National Standards Institute, Inc. (ANSI/DHI) publications:   

A1 5. l Preparation for Mortise Locks for 1 3/8 Inch and 1‐ 3/4 Inch. 

Doors.A115.2 Preparation for Bored Locks for 1 3/4 Inch and 1 3/8 Inch Doors. 

A115.4 Preparation for Lever Extension Flush Bolts. 

Al15.5 Preparation for 181 Series and 190 Series Deadlock Strikes. 

All5.7 Preparation for Floor Closers ‐‐ Light Duty, Center Hung, Single or 
Double Acting; Center Hung, Single or Double Acting; Offset Hung, Single 
Acting. 

American National Standards Institute, Inc. (ANSI/SDI) Publications: 

100 Recommended Specifications ‐ Standard Steel Doors and Frames. 

A151.1 Test Procedure and Acceptance Criteria for Physical Endurance for 
Steel Doors and Hardware Reinforcing. 

FAA‐C90‐420 
23 November, 2021 

National Fire Protection Association (NFPA) Publications: 

Fire Doors and Windows. 

Fire Tests of Door Assemblies. 

Life Safety Code. 

Steel Door Institute (SDI) Publications: 

SDI‐100 

Standard Steel Doors and Frames. 

Recommended Erection Instructions for Steel Frames 
Hardware on Steel Doors (Reinforcement ‐ Application) 
Recommended Standard Details for Dutch  Doors. 
 Recommended Completed Opening Anchors for Standard 
Steel Doors and Frames. 

Underwriters  Laboratories,  Inc.  (UL)  Publication: lOB 

Fire test of Door assemblies. 

Swinging Hardware for Standard Tin‐Clad Fire Doors Mounted 
Singly and in Pairs. 

Building Materials Directory (January 1983) 

American National Standards Institute (ANSI/BHMA) Publications: 

A156.1 

Butts and Hinges. 

A156.2 

Bored and Preassembled Locks and Latches . 

A156.3 

Exit Devices. 

A156.4. 

Door Controls –  Closers. 

A156.5 

Auxiliary Locks and Associated Products.  

A156.7 

Architectural Door Trim. 

FAA‐C90‐420 
23 November, 2021 

A156.8 

A156.9 

    Template Hinge Dimensions. 

    Door Controls ‐ Overhead Holders. 

A156.13 

  Mortise Locks and Latches. 

A156.15 

Life Safety Closer/Holder/Release Devices. 

A156.16 

Auxiliary Hardware. 

A156.17 

 Self‐Closing Hinges and Pivots. 

.A156.18 

Materials and Finishes. 

1.03 QUALITY ASSURANCE 

A. Use only qualified installers for installing the new doors and hardware. 
Upon request submit evidence that key personnel have successfully 
performed similar work within the past three (3) years. 

B. Conform to the respective standards listed and to requirements specified 
herein. Doors and hardware shall be clearly and permanently marked 
with the manufacturer's name or trademark where it will be visible after 
the item is installed.  For closers with covers, the name or trademark may 
be beneath the cover.  Provide hardware items as specified below and as 
l listed in this statement of work and this section, 1.01(B). 

1.04 REGULATORY REQUIREMENTS 

A. References Section 00 11 10 of this statement of work. 

1.05

SUBMITTALS. 

A. Reference Appendix I of this statement of work for submittal requirements. 

FAA‐C90‐420 
23 November, 2021 

1.06 DELIVERY AND STORAGE. 

A. Deliver doors, frames, hardware, and accessories undamaged and with 
protective wrappings or packaging. Strap welded frames in pairs, with 
one frame inverted, or provide temporary steel spreaders securely 
fastened to the bottom of each frame. Store doors and frames on 
platforms under covers in a dry and ventilated location. Protect new 
hardware from damage, including damage to new finish. Remove damp 
or wet packaging immediately and wipe affected surfaces dry. 
Replace damaged materials with new approved by the COR. 

FAA‐C90‐420 
23 November, 2021 

PART 2 ‐ PRODUCTS 

2.01 STANDARD STEEL DOORS 

A. ANSI/SDI 100, except as specified otherwise. Doors shall be insulated hollow 
steel construction or composite construction. Prepare doors to receive new 
hardware specified in this section. Undercut doors where indicated. Exterior 
doors shall have top edge closed flush and be shall be 1 3/4 inches thick with 
16 GA sheet metal face, fire rated for 1‐1/2 hours. 

B. Insulated steel doors to be provided at all exterior doors. Doors to be 

ANSI/SDI, Grade III, Model 3 or 4 of sizes and designs indicated. Insulated steel 
doors shall have a core of polyurethane foam and an R factor of 10. 

C. Rigid Polyurethane Foam: ASTM C591, Type 1 or 2, foamed‐in‐place or in 

board form, with an oxygen index of not less than 22 percent when tested 
in accordance with ASTM D2863  or Rigid Polystyrene Foam Board: ASTM 
C578, Type I or II. 

2.02 STEEL FRAMES 

A. ANSI/SDI 100, except as otherwise specified. Form frames to sizes and 

shapes indicated, with knock‐down field‐assembled corners. Provide steel 
frames for doors, sidelights, mullions, interior glazed panels, as indicated. 
Provide standard steel frames at interior and heavy duty frames at exterior. 

B. Welded Frames: Continuously weld frame faces at corner joints. 

Mechanically interlock or continuously weld stops and rabbits. Grind 
welds smooth. 

C. Stops and Beads: Form stops and beads from 20‐gauge steel. Provide for 
glazed and other openings in standard steel frames. Secure beads to 
frames with oval‐head, countersunk Phillips‐head self‐tapping sheet metal 
screws or concealed clips and fasteners. Space fasteners approximately 12 
to 16 inches on‐center. Miter molded shapes at corners. Butt or miter 
square or rectangular beads at corners. 

D. Anchors: Provide anchors to secure the frame to adjoining 

construction. Provide  steel  anchors,  zinc‐coated  or  painted  with rust‐ 
inhibitive paint, not lighter than 18 gauge. 

FAA‐C90‐420 
23 November, 2021 

E. Wall Anchors: Provide a minimum of three anchors for each jamb. 
Locate anchors opposite top and bottom hinges and midway 
between. 

F. Stud Partitions: Weld or otherwise securely fasten anchors to backs of 
frames. Design anchors to be fastened to closed steel studs with sheet 
metal screws, and to open steel studs by wiring or welding; 

G. Completed Openings: Secure frames to previously placed precast 
concrete with expansion bolts in accordance with SDI 111 ‐F. 

H. All steel frames to be fully grouted. 

I. Floor Anchors: Provide floor anchors drilled for 3/8‐inch anchor bolts at 

bottom of each jamb member. Where floor fill occurs, terminate bottom 
of frames at the indicated finished floor levels and support by adjustable 
extension clips resting on and anchored to the structural slabs. 

J. Head Anchors:  Provide 2 head anchors at centerline of each pair of doors. 

2.03 FIRE DOORS AND FRAMES 

A. The requirements of NFPA 80 shall take precedence over details indicated or 

specified. 

B. Labels: Fire doors and frames shall bear the label of Underwriters 

Laboratories, Inc. (UL), Factory Mutual Engineering Corporation (FM), or 
Warnock Hersey International (WHI) attesting to the rating required. Testing 
shall be in accordance with NFPA 252 or UL lOB. Labels shall be metal with 
raised letters, and shall bear the name or file number of the door and frame 
manufacturer. Labels shall be permanently affixed at the factory to frames 
and to the hinge edge of the door.  Door labels shall not be  painted. 

C. Steel Astragal on Rated Fire Doors: Astragal on pairs of labeled fire doors 

shall conform to NFPA 80 and UL requirements. 

D. Hardware for Fire Doors and Exit Doors: NFPA 80 for fire doors and NFPA 
101 for exit doors, in addition to other requirements specified. Such 
hardware shall bear the UL label and be listed in UL Building Materials 
Directory for class of door required. 

FAA‐C90‐420 
23 November, 2021 

A. ASTM C1036, Type II, Class 1, Quality 98, 6Mm thick, form 1 polished 

2.04 WIRE GLASS 

wire glass, Mesh M2. 

2.05 DOOR FINISHES 

A. Factory‐Primed Finish:  Unless specified otherwise, phosphate treat and 
factory prime metal doors and frames as specified in ANSI/SDI 100. 

B. Fabricate doors and frames from electrolytic zinc‐coated steel, ASTM A591, 

Commercial Quality, Coating Class A. Phosphate treat and factory prime zinc‐ 
coated surfaces as specified in ANSI/SDI 100. 

C. Field paint doors and frames to match the existing door color. For each 
door apply 2 coats of compatible finish paint. The finish paint shall be of 
an exterior finish coat recommended for use on primed stee