CNIC-31 – NRW 987, Replace Fire Pull Station and Investigate Fire System PRI 1 Remove and replace in kind (2) manual pull stations, update FACP reporting of heat detector in the kitchen above the FACP, and investigate fire devices for deficiencies.
Type: Forecast
Overview
Description
TR performed an Annual Test and Inspection of the Fire Alarm system. KTR proposes the following to correct the noted deficiencies:
1. FACP had (1) supervisory for zone 4 kitchen ducts at arrival - Investigate supervisory
2. Duct detector Kitchen Area D.1 Supply - Did not perform shutdown of ahu - investigate issue
3. RTU.1 HVAC-Shutdown - did not shutdown - investigate shutdown issues
4. Heat detector Kitchen Above FACP - reports to panel as manual station, change to report as heat detector
5. Manual Pull Station Side Entrance - Did not activate - replace manual station
6. Manual Pull Station Main Entrance - Did not activate - replace manual station
Est. Value
<$2,000,000
Est. Award Date
Q4 2026
Source Est. Solicitation Date
Q4 2026
Set Aside
Sole-Source
Pricing
Fixed-Price
Procurement Method
TBD
Forecast Type
New
Place of Performance
USA
Forecast Source
Naval Facilities Engineering Command
NAVFAC Washington is forecasted to issue a new procurement for CNIC-31 – NRW 987, Replace Fire Pull Station and Investigate Fire System PRI 1
Remove and replace in kind (2) manual pull stations, update FACP reporting of heat detector in the kitchen above the FACP, and investigate fire devices for deficiencies. around Q4 2026 worth up to $2,000,000.
Agency
Source Level 1 Agency
Naval Facilities Engineering Command
Source Level 2 Agency
NAVFAC Washington
Source Level 3 Agency
N40080
Contacts
Potential Bidders and Partners
Similar Active Opportunities
Additional Detail
Date Published
12/22/25
Additional Notes
BOS and Sole Source