Modification to a Previous Notice
SUBJECT* 691-23-1-5091-0008 | ATS/IR/Electrical Panel Annual Inspection | GLA
GENERAL INFORMATION
CONTRACTING OFFICES ZIP CODE*
SOLICITATION NUMBER*
BASE NOTICE TYPE
RESPONSE DATE/TIME/ZONE
ARCHIVE
RECOVERY ACT FUNDS
SET-ASIDE
PRODUCT SERVICE CODE*
NAICS CODE*
CONTRACTING OFFICE ADDRESS
POINT OF CONTACT*
85297
36C26223Q004803-01-2023 13:00 PACIFIC TIME, LOS ANGELES, USA
30 DAYS AFTER THE RESPONSE DATESDVOSBC238210
NCO 22
Department of Veterans Affairs
NCO 22 - Gilbert Network Contracting
335 East Germann Road
Gilbert AZ 85297
Contract Specialist
Edward Condreay
edward.condreay@va.gov
858-209-1532
ADDRESS
POSTAL CODE
COUNTRY
PLACE OF PERFORMANCE
Department of Veterans Affairs
Greater Los Angeles VA Health Care System
Sepulveda VA Medical Campus
16111 Plummer St.
Los Angeles CA
91343-2036
ADDITIONAL INFORMATION
AGENCYS URL
URL DESCRIPTION
AGENCY CONTACTS
EMAIL ADDRESS
EMAIL DESCRIPTION
https://www.va.gov/greater-los-angeles-health-care/locations
Sepulveda VA Medical Center
https://www.desertpacific.va.gov/DESERTPACIFIC/NetworkContra
Network Contracting Office 22
*= Required Field
Modification to a Previous Notice
Modification to a Previous Notice
DESCRIPTION
SUBJECT
691-23-1-5091-0008 | ATS/IR/Electrical Panel Annual Inspection | GLA
GENERAL INFORMATION
CONTRACTING OFFICES ZIP CODE
SOLICITATION NUMBER
ARCHIVE
RECOVERY ACT FUNDS
PRODUCT SERVICE CODE
NAICS CODE
CONTRACTING OFFICE ADDRESS
POINT OF CONTACT
90815
36C26223Q0048
30 DAYS AFTER THE RESPONSE DATEH959
238210
Department of Veterans Affairs
Network Contracting Office 22
4811 Airport Plaza Drive
Suite 600
Long Beach CA 90815
Contract Specialist
Edward Condreay
edward.condreay@va.gov
ADDITIONAL INFORMATION
AGENCYS URL
URL DESCRIPTION
AGENCY CONTACTS EMAIL ADDRESS
EMAIL DESCRIPTION
Modification to a Previous Notice
Special Notice
DESCRIPTION
Greater Los Angeles Industry Outreach Event
For Annual Electrical Inspection of Infra-Red, EMD (Electro-Motor Diesel) Emergency
Generators and ATS (Automatic Transfer Switches)
1. Scope:
Engineering Services at Greater Los Angeles VA Healthcare System, Sepulveda VA Medical
Campus located at 16111 Plummer St., North Hills, CA, are interested in seeking industry
input for the Statement of Work provided within this announcement.
The Facility is requesting industry participants within NAICS CODE: 238210 (Electrical
Contractors and Other Wiring Installation Contractors) for input and refinement of the
Statement of Work to parallel industry standards. This contract would be a Base plus (4) Four
Year Options once a viable Statement of Work has been established.
The current Statement of Work is provided in the following pages of this announcement.
Industry Outreach Event:
The site tour of the area where electrical panels, IR Surveys, ATS and EMD Inspections will be
conducted on Wednesday, 02/23/2023 at 1300/PST (1:00PM/PST). Vendors will coordinate at
the main facility located at 16111 Plummer St., North Hills, CA 91343.
In order to participate in this event, interested vendors must RSVP by emailing one of the
parties below NLT Tuesday, 02/21/2023 at 1300/PST (1:00PM/PST).
Edward Condreay, Contract Specialist, NCO 22 (Remote)
o Email: edward.condreay@va.gov
All questions arising from this Industry Day, shall be submitted in writing via email to the
following parties below NLT Thursday, 03/02/2023.
Edward Condreay, Contract Specialist, NCO 22 (Remote)
Email: edward.condreay@va.gov
Helena Roba, Contracting Officer, NCO 22 (Remote)
Email: helena.roba@va.gov
Responses to the questions submitted shall be posted NLT Wednesday, 03/08/2023.
Please note: This advertisement is not a request for proposals only information for future
procurement.
Special Notice
Special Notice
Department of Veterans Affairs
Engineering Department
16111 Plummer Street
North Hills, CA 91343
STATEMENT OF WORK
as of October 13, 2022
Name:
Section:
Address:
Emergency Generators, Automatic Transfer Switches (ATS), Maintenance
and Testing. IR Thermography of Electrical Panels and Transformers within
Buildings.
Engineering 138
16111 Plummer street North Hills, CA 91343
1. Contract Title:
2. Background:
3. Scope:
Emergency Generators, Automatic Transfer Switches (ATS) Testing and IR Thermography
VHA Directive 1028 and NFPA 110 require Emergency Generators and Automatic Transfer
Switch (ATS) to be tested as well as Thermography performed on an Annual Basis.
Annual Maintenance, Testing of Electrical Grid Automatic Transfer Switches (ATS), Breakers
at Infrared Thermography for Sepulveda and LAOPC campus Using NFPA 110
4. Technical Requirements:
a. Vendor shall have experience on an EMD emergency power generator,
b. Specialist in various Generator Manufacturers,
c. ATS testing and repairs for at least 10 years.
d. Vendor shall provide references and a list of past projects completed.
5. Specific Tasks:
Test and Inspect Emergency Generators and Automatic Transfer Switches (ATS)
Scope of Work for Generator Inspection
Engine and Oil
Check oil level and fill as needed, record amount replaced.
Check oil heater for proper operation and leaks
Check all belts for excessive wear, cracks and adjust if needed
Check all ignition wires and distributer cracks, corrosion and carbon tracking
Special Notice
Special Notice
Check engine and alternator vibration mounts for wear and alignment
Check oil system and engine seals for leakage.
Check governor for proper operation and adjust as needed.
Check governor linkage lubricate and adjust as needed
Check governor oil level and add if needed
Check pillow block bearings for wear and lubricate as needed Cooling System
Check coolant level and fill as needed
Check DCA coolant levels, freeze point protection and make recommendations as needed
Check cooling system for signs of leakage
Check jacket water heater for proper operation and leaks
Check for pliability and cracks of all coolant hoses
Check radiator for leaks and correct water flow and air flow
Check for proper operation of solenoid valves and leaks
Check and lubricate cooling system fan
Check louver operation and adjust if needed
Check radiator cap and seals for cracks and leaks Fuel Systems
Check injector pump lines for leaks
Check injector supply and return for cracks leaks and pliability
Check proper operation of lift pump
Check Water Separator and drain if needed
Check and record main fuel tank level
Check for proper day tank operation and fuel level Battery and Starting System
Check and record minimum crank voltage
Check start solenoid terminals for corrosion and tighten if needed
Check starter for proper operation
Clean, treat all battery terminals for corrosion and tighten if needed
Check battery fluid levels and add if needed
Check and record alternator voltage
Check, record battery charger voltage and adjust if needed Intake System
Check all hoses and clamps for leaks, pliability and tighten if needed
Check turbo charger connection for leaks and tighten if needed
Check condition of Air filter
Exhaust Systems
Check flexible exhaust pipes for leaks, cracks and corrosion
Drain condensation from exhaust silencer
Check proper operation of rain cap
Check all exhaust piping for leaks, oil slobbering and corrosion
Check exhaust manifold for leaks, oil slobbering and corrosion Electrical
Check control panel relays for proper operation and corrosion
Check solid state circuits for proper operation and corrosion
Special Notice
Special Notice
Check exciter for proper operation
Check rotating diodes for proper operation and corrosion
Check all electrical connections for corrosion, cracked insulation and tighten if needed
Scope of Work for Annual Generator Service
Engine and Oil
Drain and replace engine oil
Replace oil filters
Take oil sample for oil analysis and report back if needed Testing
shall be for wear metals, contaminate metals, additive metals and multisource metals
Check oil heater for proper operation and leaks
Check all belts for excessive wear, cracks and adjust if needed
Check all ignition wires and distributer cracks, corrosion and carbon tracking
Check engine and alternator vibration mounts for wear and alignment
Check oil system and engine seals for leakage.
Check governor for proper operation and adjust as needed.
Check governor linkage lubricate and adjust as needed
Check governor oil level and add if needed
Check pillow block bearings for wear and lubricate as needed Cooling System
Change coolant filter as needed
Check coolant level and fill as needed
Check DCA coolant levels, freeze point protection and make recommendations as needed
Check cooling system for signs of leakage
Check jacket water heater for proper operation and leaks
Check for pliability and cracks of all coolant hoses
Check radiator for leaks and correct water flow and air flow
Check for proper operation of solenoid valves and leaks
Check and lubricate cooling system fan
Check louver operation and adjust if needed
Check radiator cap and seals for cracks and leaks Fuel Systems
Replace fuel filters
Prime fuel system prior to starting
Check injector pump lines for leaks
Check injector supply and return for cracks leaks and pliability
Check proper operation of lift pump
Check Water Separator and drain if needed
Check and record main fuel tank level
Check for proper day tank operation and fuel level Battery and Starting System
Check and record minimum crank voltage
Check start solenoid terminals for corrosion and tighten if needed
Check starter for proper operation
Special Notice
Special Notice
Clean, treat all battery terminals for corrosion and tighten if needed
Check
SUBJECT* 691-23-1-5091-0008 | ATS/IR/Electrical Panel Annual Inspection | GLA
GENERAL INFORMATION
CONTRACTING OFFICES ZIP CODE*
SOLICITATION NUMBER*
BASE NOTICE TYPE
RESPONSE DATE/TIME/ZONE
ARCHIVE
RECOVERY ACT FUNDS
SET-ASIDE
PRODUCT SERVICE CODE*
NAICS CODE*
CONTRACTING OFFICE ADDRESS
POINT OF CONTACT*
85297
36C26223Q004803-01-2023 13:00 PACIFIC TIME, LOS ANGELES, USA
30 DAYS AFTER THE RESPONSE DATESDVOSBC238210
NCO 22
Department of Veterans Affairs
NCO 22 - Gilbert Network Contracting
335 East Germann Road
Gilbert AZ 85297
Contract Specialist
Edward Condreay
edward.condreay@va.gov
858-209-1532
ADDRESS
POSTAL CODE
COUNTRY
PLACE OF PERFORMANCE
Department of Veterans Affairs
Greater Los Angeles VA Health Care System
Sepulveda VA Medical Campus
16111 Plummer St.
Los Angeles CA
91343-2036
ADDITIONAL INFORMATION
AGENCYS URL
URL DESCRIPTION
AGENCY CONTACTS
EMAIL ADDRESS
EMAIL DESCRIPTION
https://www.va.gov/greater-los-angeles-health-care/locations
Sepulveda VA Medical Center
https://www.desertpacific.va.gov/DESERTPACIFIC/NetworkContra
Network Contracting Office 22
*= Required Field
Modification to a Previous Notice
Modification to a Previous Notice
DESCRIPTION
SUBJECT
691-23-1-5091-0008 | ATS/IR/Electrical Panel Annual Inspection | GLA
GENERAL INFORMATION
CONTRACTING OFFICES ZIP CODE
SOLICITATION NUMBER
ARCHIVE
RECOVERY ACT FUNDS
PRODUCT SERVICE CODE
NAICS CODE
CONTRACTING OFFICE ADDRESS
POINT OF CONTACT
90815
36C26223Q0048
30 DAYS AFTER THE RESPONSE DATEH959
238210
Department of Veterans Affairs
Network Contracting Office 22
4811 Airport Plaza Drive
Suite 600
Long Beach CA 90815
Contract Specialist
Edward Condreay
edward.condreay@va.gov
ADDITIONAL INFORMATION
AGENCYS URL
URL DESCRIPTION
AGENCY CONTACTS EMAIL ADDRESS
EMAIL DESCRIPTION
Modification to a Previous Notice
Special Notice
DESCRIPTION
Greater Los Angeles Industry Outreach Event
For Annual Electrical Inspection of Infra-Red, EMD (Electro-Motor Diesel) Emergency
Generators and ATS (Automatic Transfer Switches)
1. Scope:
Engineering Services at Greater Los Angeles VA Healthcare System, Sepulveda VA Medical
Campus located at 16111 Plummer St., North Hills, CA, are interested in seeking industry
input for the Statement of Work provided within this announcement.
The Facility is requesting industry participants within NAICS CODE: 238210 (Electrical
Contractors and Other Wiring Installation Contractors) for input and refinement of the
Statement of Work to parallel industry standards. This contract would be a Base plus (4) Four
Year Options once a viable Statement of Work has been established.
The current Statement of Work is provided in the following pages of this announcement.
Industry Outreach Event:
The site tour of the area where electrical panels, IR Surveys, ATS and EMD Inspections will be
conducted on Wednesday, 02/23/2023 at 1300/PST (1:00PM/PST). Vendors will coordinate at
the main facility located at 16111 Plummer St., North Hills, CA 91343.
In order to participate in this event, interested vendors must RSVP by emailing one of the
parties below NLT Tuesday, 02/21/2023 at 1300/PST (1:00PM/PST).
Edward Condreay, Contract Specialist, NCO 22 (Remote)
o Email: edward.condreay@va.gov
All questions arising from this Industry Day, shall be submitted in writing via email to the
following parties below NLT Thursday, 03/02/2023.
Edward Condreay, Contract Specialist, NCO 22 (Remote)
Email: edward.condreay@va.gov
Helena Roba, Contracting Officer, NCO 22 (Remote)
Email: helena.roba@va.gov
Responses to the questions submitted shall be posted NLT Wednesday, 03/08/2023.
Please note: This advertisement is not a request for proposals only information for future
procurement.
Special Notice
Special Notice
Department of Veterans Affairs
Engineering Department
16111 Plummer Street
North Hills, CA 91343
STATEMENT OF WORK
as of October 13, 2022
Name:
Section:
Address:
Emergency Generators, Automatic Transfer Switches (ATS), Maintenance
and Testing. IR Thermography of Electrical Panels and Transformers within
Buildings.
Engineering 138
16111 Plummer street North Hills, CA 91343
1. Contract Title:
2. Background:
3. Scope:
Emergency Generators, Automatic Transfer Switches (ATS) Testing and IR Thermography
VHA Directive 1028 and NFPA 110 require Emergency Generators and Automatic Transfer
Switch (ATS) to be tested as well as Thermography performed on an Annual Basis.
Annual Maintenance, Testing of Electrical Grid Automatic Transfer Switches (ATS), Breakers
at Infrared Thermography for Sepulveda and LAOPC campus Using NFPA 110
4. Technical Requirements:
a. Vendor shall have experience on an EMD emergency power generator,
b. Specialist in various Generator Manufacturers,
c. ATS testing and repairs for at least 10 years.
d. Vendor shall provide references and a list of past projects completed.
5. Specific Tasks:
Test and Inspect Emergency Generators and Automatic Transfer Switches (ATS)
Scope of Work for Generator Inspection
Engine and Oil
Check oil level and fill as needed, record amount replaced.
Check oil heater for proper operation and leaks
Check all belts for excessive wear, cracks and adjust if needed
Check all ignition wires and distributer cracks, corrosion and carbon tracking
Special Notice
Special Notice
Check engine and alternator vibration mounts for wear and alignment
Check oil system and engine seals for leakage.
Check governor for proper operation and adjust as needed.
Check governor linkage lubricate and adjust as needed
Check governor oil level and add if needed
Check pillow block bearings for wear and lubricate as needed Cooling System
Check coolant level and fill as needed
Check DCA coolant levels, freeze point protection and make recommendations as needed
Check cooling system for signs of leakage
Check jacket water heater for proper operation and leaks
Check for pliability and cracks of all coolant hoses
Check radiator for leaks and correct water flow and air flow
Check for proper operation of solenoid valves and leaks
Check and lubricate cooling system fan
Check louver operation and adjust if needed
Check radiator cap and seals for cracks and leaks Fuel Systems
Check injector pump lines for leaks
Check injector supply and return for cracks leaks and pliability
Check proper operation of lift pump
Check Water Separator and drain if needed
Check and record main fuel tank level
Check for proper day tank operation and fuel level Battery and Starting System
Check and record minimum crank voltage
Check start solenoid terminals for corrosion and tighten if needed
Check starter for proper operation
Clean, treat all battery terminals for corrosion and tighten if needed
Check battery fluid levels and add if needed
Check and record alternator voltage
Check, record battery charger voltage and adjust if needed Intake System
Check all hoses and clamps for leaks, pliability and tighten if needed
Check turbo charger connection for leaks and tighten if needed
Check condition of Air filter
Exhaust Systems
Check flexible exhaust pipes for leaks, cracks and corrosion
Drain condensation from exhaust silencer
Check proper operation of rain cap
Check all exhaust piping for leaks, oil slobbering and corrosion
Check exhaust manifold for leaks, oil slobbering and corrosion Electrical
Check control panel relays for proper operation and corrosion
Check solid state circuits for proper operation and corrosion
Special Notice
Special Notice
Check exciter for proper operation
Check rotating diodes for proper operation and corrosion
Check all electrical connections for corrosion, cracked insulation and tighten if needed
Scope of Work for Annual Generator Service
Engine and Oil
Drain and replace engine oil
Replace oil filters
Take oil sample for oil analysis and report back if needed Testing
shall be for wear metals, contaminate metals, additive metals and multisource metals
Check oil heater for proper operation and leaks
Check all belts for excessive wear, cracks and adjust if needed
Check all ignition wires and distributer cracks, corrosion and carbon tracking
Check engine and alternator vibration mounts for wear and alignment
Check oil system and engine seals for leakage.
Check governor for proper operation and adjust as needed.
Check governor linkage lubricate and adjust as needed
Check governor oil level and add if needed
Check pillow block bearings for wear and lubricate as needed Cooling System
Change coolant filter as needed
Check coolant level and fill as needed
Check DCA coolant levels, freeze point protection and make recommendations as needed
Check cooling system for signs of leakage
Check jacket water heater for proper operation and leaks
Check for pliability and cracks of all coolant hoses
Check radiator for leaks and correct water flow and air flow
Check for proper operation of solenoid valves and leaks
Check and lubricate cooling system fan
Check louver operation and adjust if needed
Check radiator cap and seals for cracks and leaks Fuel Systems
Replace fuel filters
Prime fuel system prior to starting
Check injector pump lines for leaks
Check injector supply and return for cracks leaks and pliability
Check proper operation of lift pump
Check Water Separator and drain if needed
Check and record main fuel tank level
Check for proper day tank operation and fuel level Battery and Starting System
Check and record minimum crank voltage
Check start solenoid terminals for corrosion and tighten if needed
Check starter for proper operation
Special Notice
Special Notice
Clean, treat all battery terminals for corrosion and tighten if needed
Check
Show All