DOCUMENT

001 SOW FIBER WRBR.pdf

OVERVIEW

Original Source
Contract Opportunity
Related Agency
Date Originally Posted
July 14, 2021, 4:27 p.m.
Type
.pdf
Size
0.56MB
Profiled People
None

DOCUMENT PREVIEW

EXTRACTED TEXT

NATIONAL PARK SERVICE (NPS)
SOUTHEAST REGION
Wright Brothers National Memorial (WRBR)
Fiber optic cabling and raceway installation
STATEMENT OF WORK (SOW)

General
This project is for the installation of underground fiber optic infrastructure between buildings to
create a campus environment. This project will connect the Wright Brothers National Memorial
(WRBR) Visitor Center network room to network cabinets inside both the large and small fee
booths and to the network cabinet in the office trailer. The project includes all labor, supplies,
materials, and testing necessary to create a fully functional fiber optic network between these
four buildings. It is the responsibility of the contractor to provide a fully functioning network
infrastructure from end to end (fiber optic patch panel to fiber optic patch panel) for each
building within the campus. Acceptance of the completed work will be based on an acceptable
Bi-Directional OTDR test that falls within the specified limits. This scope of work describes the
minimum level of performance required by the government. All equipment must be new and
unused. *Connecting non-government devices to the government data network is strictly
prohibited! All technicians performing work must be certified to install and terminate fiber. All
work shall be done in accordance with the attached National Park Service Cabling Standards for
all data network cabling specifications and installation requirements. The Wright Brothers
Visitor Center is a National Historic Site.

Locations:

(1) Wright Brothers Visitor Center, 1000 North Croatan Hwy, Kill Devil Hills, NC 27948
(2) Large Ticket Booth, 1001 North Croatan Hwy, Kill Devil Hills, NC 27948
(3) Small Ticket Booth, 1002 North Croatan Hwy, Kill Devil Hills, NC 27948
(4) Office Trailer, 1003 North Croatan Hwy, Kill Devil Hills, NC 27948

1.1 Requirements and Specifications

1.1.1 HDPE Installation Under Ground

a. Install approximately 2,400 linear feet of 1.25” HDPE roll pipe between the

four locations listed in the location section.

b. This consist of approximately 600’ of Directional boring and 1,800’ of open

trench/plow.

c. HDPE will follow the mapped path on “WRBR Area Map 1” along parking,

roads, and walkways within a 5’ offset.

d. HDPE will have a minimum 30” off set from any existing utilities.
e. Directional bore will be at minimum 24” and maximum 48” from existing

grade. Open trench/plow footage will be at minimum 24” and Maximum 36”

from existing grade. Depths more than the maximum stated must be used
when necessary, to avoid or cross existing utilities that are in direct path of
project.

f. Contractor to locate utilities outside of buildings and ensure that they are not
damaged in the process of horizontal drilling and/ or trenching/plowing.
g. All directional bore gel will need to be contained with silt fences and removed

as part of site restoration.

1.1.2 Polymer Concrete Box Installation

a. Contractor shall provide and install four (4) polymer concrete in-ground vaults.
b. Vaults will be installed in the locations specified on area map 1.
c. Dimensions must be 30”x48”x18”
d. Vaults must be traffic rated.
e. Pea gravel will be placed as base for drainage and support.
f. All fiber vaults will have a total of 50’ of stored fiber in each direction (100’ for

coils) and 50’ storage coil for lateral cables.

g. HDPE is required to enter the vaults and will be trimmed 6” above gravel base,

and pipe must be sealed after fiber cable has been placed.

1.1.3 Provide and install cabling

a. The contactor shall provide and install 24 strand, single mode loose tube fiber

optic cable following routes on WRBR Area Map 1.

b. Must meet or exceed NPS-Cable-Standard-v-1.0 (appendix A)
c. 100% of all fiber must be installed in newly HDPE roll pipe and conduit up to

each network cabinet

d. Must be terminated using Active Core Alignment Fusion splicing.
e. Must use pre-terminated Fiber Optic pigtails with SC/UPC connectors.
f. Service loops must be created at each of the four vaults by leaving 100’ coil
g. Service loops must be created at each network cabinet by leaving 20’ coil
h. Cables will terminate by the contractor at contractor supplied 1U, 24 count rack
mount Optical Patch Panel (OPP) in each building as planned in cable path.

i. All strands of fiber must be terminated at each termination box

1.1.4 Riser Conduit installation

a. All risers into and out of buildings will use 1.25” schedule 40 conduit and

sweeping 90 degree when turns are necessary, to adhere to fiber optic cable
bend radius specs. LB, and pull junction boxes are acceptable. All conduit
installation should meet electrical NC State codes, Dare County codes, and NPS
Cable-Standard-v-1.0 (Appendix A)

b. At the large ticket booth, riser up 10’ into eave, enter attic space and drop down
into new Network Cabinet (1.1.6). Terminate fiber into 1U 24ct rack panel. From
there a new fiber will be pulled up and trough attic to exist as drawings show.
Riser down 10” with 1.25” conduit and proceed to ticket booth #2 (secondary

booth) as map drawings show. The large ticket booth will feed the small ticket
booth network.

c. Bore drive as shown and riser up ticket booth #2. Into eave and into attic. Drop
down into new Network cabinet Terminate Fiber into 1U 24ct Rack panel.
d. Stubbed conduit will need to be sealed to avoid moisture and rodent intrusion.

All building entrances will need to be weather caulked and sealed using fire rated
caulk.

e. Contactor shall core drill into exterior of the building to the minimum extent

required to allow for conduit.

f. At Office Trailer South side of park as shown on map, Schedule 40 conduit will be
placed alongside existing conduit and follow path 125’ into Trailer. Enter trailer
underside and into IT room. Riser up and seal conduit. Fiber will terminate in
New Network Cabinet with 1U 24ct Rack Panel.

1.1.5 Fiber Optic Fusion Splicing

a. Fusion splicing will be performed on all cable ends and termination panels. Using

Core Alignment Fusion Splice machines.

b. Individual splice loss shall not exceed .15db, bi-directional. And connector loss
shall not exceed .35db, per industry standards. Post processing will need to be
furnished in .SOR and .PDF format.

c. All cables will need to be properly bonded and grounded to industry standards.
d. Trayed fiber splices should be clean and not to exceed 3” bend radius per

industry standards. Improper fiber strand management will not be accepted.
e. Pictures must be provided of all splice tray conditions upon completion, and

inspection of these panels and trays will be performed by supervising
coordinator.

f. Contractor must follow the splice plans in Appendix B

1.1.6 Network Cabinets

a. The contractor shall provide and install (3) 6U wall mount lockable rack
enclosures, Dell (Tripp Lite SRW6UG) or equivalent with the following
dimensions: 23.5 in x 17.5 in x 14.5 in

b. Must be standard 19” rack assembly adjustable rails.
c. All network enclosures will need to installed on contractor supplied plywood

backboard. Backboard will be anchored securely to structured wall supports. And
will be ¾” Cabinet grade plywood. It must to be lagged to studs and support up
to 200lbs. as indicated in cabinet specs of this size.

1.1.7 Provide and Install Fiber Optic Patch Panels (OPP)

a. Provide and install (4) 24ct fiber optic patch panels (OPP), one at each network

cabinet and one in existing visitor center rack.

b. Panels will be 1U 19” 24ct, rack mount patch panel and compatible with

contractor supplied cabinets.

c. All fiber optic rack panels must be installed at the top of the network cabinet in

the first position down, allowing room for network switches and equipment to
be installed working down from the optical patch panel (OPP).

d. Panels will be supplied and loaded with SC/UPC adaptor plates by contractor and
will have pre-terminated pigtails used fusion splice cables placed by contractor.

1.1.8 Fiber Optic Splice Enclosures
One (1) fiber optic splice enclosure located in the vault nearest to the large fee booth
which allows for service to the fee booths and a continuous run to the office trailer.
All fiber optic splice closures placed will be industry standard outside plant buried fiber
optic splice enclosures, Commscope FOSC450-D36G or equivalent in specs. Closures
must be properly bonded and grounded to industry specifications and standards. Locate
lugs must be placed on ground lugs for locating purposes.

1.1.9 Applicable Standards and Regulations
The Contractor shall conform to, and be compliant with all applicable Federal Communications
Commission (FCC) rules and regulations, local construction codes, and established industry
standards. The standards shall be applied during the engineering, fabrication, assembly, wiring,
installation, testing, operation, maintenance, and management of the system(s) or service(s). If
a conflict arises between standards, the contractor shall submit written requests for
clarification citing the specific particulars to the Contracting Officer. The Contracting Officer will
respond with written direction.

1.1.10 Site Access
The NPS issues access to government property via Special Use Permits and via escorts as
needed. The contractor shall initiate and coordinate all necessary special use permit or access
approvals no later than 2 weeks before the project’s start date.

The contractor shall restore walls, ceilings, and floors if they become damaged by contractor or
sub-contractor employees. The restoration must bring the worksite to the appearance and
condition that existed prior to the work being performed.

The contractor is also responsible for cleanup, removal, and disposal of any debris associ