Description

All questions are due by 17 Sept 2024, 1200 MT. At this time, there is no site visit scheduled. The Government will establish a date if needed.

Purchase, deliver, and install sixteen (16) seismic compliant IT Cabinet Racks in two hot aisle containment (HAC) configurations.
Each HAC will have two rows of four cabinets for a total of eight cabinets per HAC.
Each rack shall be fitted with a brush grommet rail kit, a copper bus bar, a vertical cable bar kit, blanking/filler panels, remote
power distribution units (rPDU), rPDU bracket sets for vertical mounting in rear cabinet corner, ganging kits for the cabinets,
and temperature sensors.
External Temperature Sensors - One (1) temperature sensors per cabinet mounted externally on the front of the cabinet to
measure incoming air and connected to the rPDU.
Internal Temperature Sensors - One (1) temperature sensor per cabinet mounted on the rear of the cabinet (the hot aisle
side) and connected to the rPDU.
Grounding the Racks - To protect personnel, equipment, and to minimize electrostatic discharge, each rack will be properly
grounded and bonded IAW Schriever AFB Instruction 17-201 and applicable military and commercial standards.
Containment Doors - Hot aisle(s) shall have containment doors mounted on each end of the hot aisle
Biometric Door Locks installed on the front and rear of each cabinet. These locks shall be networked to the main control server.
LED Strips - External rear mounted LED strips shall be placed on every other rack inside the hot aisle and connected to a
normally open (off) motion sensor for lighting inside the hot aisle containment unit. Each LED strip shall be offset from the rack
across from it.
Thermal Curtains - Thermal breakaway curtains shall be installed from top of the cabinets to the ceiling of the mod
approximately 30 inches. The curtains will break away in the event of fire and will not impede operation of any overhead
sprinklers. They shall avoid contact with the ground as to not become a tripping hazard. They shall comply with the UFC and
NFPA 75. (Include Fire Marshal direction w/ respect to sprinkler heads etc.)
Main Control Server A server with workstation, network time protocol server (Inter-Range Instrumentation Group [IRIG-B]),
and network switch (this server will also be used to control/monitor the biometric locks).
Floor Tiles - Install new floor tiles directly inside, under, and surrounding the two new HACs (excluding where floor vents shall
be placed). See Attachment A and Attachment C.
Floor Vents Install twelve 12 manually adjustable-flow floor vents, 3 facing each cold side of each HAC. These vents shall be
adjustable in vector as well as air flow output. Vents can be set and adjusted based on unique rack load.
Temperature, Airflow, and Power Measurements
Pre-installation measurements - All test equipment shall be calibrated. Measure airflow and temperature from all currently
existing vents within Mod 3 (~25), take at least 12 dispersed temperature measurements at a height of 4 feet within Mod 3.
Record these on a room schematic where measurements were taken from and provide these to the program and project
manager. With respective time stamps to correlate with power load at that time and number of people present within the mod
at that time.
Post-installation measurements - All test equipment shall be calibrated. Measure airflow and temperature from all currently
existing vents within Mod 3 (~25), take at least 12 dispersed temperature measurements at a height of 4 feet within Mod 3.
Record these on a room schematic where measurements were taken from and provide these to the program and project
manager.
These requirements are not military unique. Hot aisle containment configurations are common throughout industry, especially in
medium to large data centers. The hot aisle /cold aisle data center layout is a proven way to save energy in a data center. Hot
aisle/cold aisle layout involves lining up server racks in alternating rows with cold air intakes the fronts of servers facing
each other (the cold aisle ) and hot air exhausts the backs of servers facing each other (the hot aisle ). Raised floors are
commonly used in data centers to provide an efficient way to deliver cold air from the computer room air conditioner (CRAC) unit to server racks. [Note: SSFB Building 400 Mods have raised floors.] CRAC units direct conditioned air into the sub-flooring.
This pressurized cool air rises through perforations in floor tiles into cold aisle, where it is subsequently drawn into the front of
servers to cool them. Hot exhaust air rises from server racks in the hot aisle and returns along the ceiling back to the to the
CRAC unit intakes.

Background
The 50th Contracting Squadron at Schriever Space Force Base, Colorado, is issuing a solicitation for the design and installation of a Hot Aisle Containment System. This system aims to optimize cooling efficiency in data centers, which is critical for maintaining operational integrity and energy efficiency in IT environments.

The project involves the installation of sixteen seismic compliant IT cabinet racks configured in two hot aisle containment setups, reflecting industry standards for data center layouts.

Work Details
The contract requires the purchase, delivery, and installation of sixteen (16) seismic compliant IT Cabinet Racks in two hot aisle containment (HAC) configurations. Each HAC will consist of two rows of four cabinets, totaling eight cabinets per HAC. Specific requirements include:
- Each rack must be fitted with:
- Brush grommet rail kit
- Copper bus bar
- Vertical cable bar kit
- Blanking/filler panels
- Remote power distribution units (rPDU)
- rPDU bracket sets for vertical mounting in rear cabinet corner
- Ganging kits for the cabinets
- Temperature sensors (external and internal)
- External Temperature Sensors: One per cabinet mounted externally on the front to measure incoming air.
- Internal Temperature Sensors: One per cabinet mounted on the rear (hot aisle side).
- Grounding: Each rack must be properly grounded and bonded according to Schriever AFB Instruction 17-201 and applicable standards.
- Containment Doors: Biometric door locks installed at each end of the hot aisle.
- LED Strips: External rear-mounted LED strips connected to motion sensors for lighting inside the hot aisle.
- Thermal Curtains: Fire-resistant breakaway curtains installed from the tops of racks to the ceiling.
- Floor Tiles: New floor tiles installed directly inside, under, and surrounding the HACs.
- Floor Vents: Twelve manually adjustable-flow floor vents installed, three facing each cold side of each HAC.
- Pre-installation and post-installation measurements for airflow and temperature must be conducted with calibrated test equipment.

Place of Performance
The work will be performed at Schriever Space Force Base, Colorado.

Overview

Response Deadline
Sept. 23, 2024, 12:00 p.m. EDT (original: Sept. 20, 2024, 2:00 p.m. EDT) Past Due
Posted
Sept. 5, 2024, 1:33 p.m. EDT (updated: Sept. 20, 2024, 1:15 p.m. EDT)
Set Aside
Small Business (SBA)
Place of Performance
Colorado Springs, CO 80912 United States
Source

Current SBA Size Standard
1250 Employees
Pricing
Likely Fixed Price
Est. Level of Competition
Low
Est. Value Range
Experimental
$500,000 - $1,000,000 (AI estimate)
Signs of Shaping
88% of obligations for similar contracts within the Department of the Air Force were awarded full & open.
On 9/5/24 Space Force issued Synopsis Solicitation DCG for Hot Aisle Containment with Server Rack due 9/23/24. The opportunity was issued with a Small Business (SBA) set aside with NAICS 334111 (SBA Size Standard 1250 Employees) and PSC 7K20.
Primary Contact
Name
Pamela S. Gusta   Profile
Phone
(719) 567-3442

Secondary Contact

Name
TSgt Trenton Beavers   Profile
Phone
(719) 567-3823

Documents

Posted documents for Synopsis Solicitation DCG

Opportunity Assistant


AI Analysis

AI Generate

Incumbent or Similar Awards

Contracts Similar to Synopsis Solicitation DCG

Potential Bidders and Partners

Awardees that have won contracts similar to Synopsis Solicitation DCG

Similar Active Opportunities

Open contract opportunities similar to Synopsis Solicitation DCG

Experts for Hot Aisle Containment with Server Rack

Recommended subject matter experts available for hire

Additional Details

Source Agency Hierarchy
DEPT OF DEFENSE > DEPT OF THE AIR FORCE > AFSPC > FA2550 50 CONS PKP
FPDS Organization Code
5700-FA2550
Source Organization Code
100215790
Last Updated
Oct. 8, 2024
Last Updated By
pamela.gusta.1@spaceforce.mil
Archive Date
Oct. 8, 2024