CNIC-64, NRW779, Replace Jockey Pump Controller, PRI 1.
Type: Forecast
Overview
Description
LS Systems technician on site per customer request WO CNRYW7 (work complete under this ticket). See LS Systems
SA 47215 for details. Technician found jockey pump controller was not energized. Upon testing with voltmeter, no
outgoing or incoming voltage detected. Traced conduit to water room Electrical Panel M1, breaker located at terminal
44-46. 15amp breaker was tripped, reset breaker & tested, correct voltage across all contacts. Controller indicator light
is on but digital interface screen is blank & none of the control buttons are working (i.e. manual start, pressure
adjustments, settings). I believe the issue may be the circuit board and/or control interface.
LS Systems proposes to furnish and install a new jockey pump controller.